Hipot Tester UH28C
€2,400.00*
Details
+49 421 277 9999
The High Voltage Tester UH28C have an additional digital I/O control interface; e.g. for the use of PLC Control. Through the signals "Start / Stop, Pass / Fail and Test" it is possible to integrate them into test systems with shortest cycle time. The zero voltage channel will be turned on or off as needed for optimal protection from overvoltage of the device under test. Optional you can get the UH28C with carrying handle (holder).
Highlights
- 5kV Hipot Tester UH28C
- 500VA transformer
- Reliable burn function
- 2 instruments: current and voltage
- Potential free in accordance to EN50191
- Release current adjustable
- 2 ranges: 10mA and 100mA
- Terminals (PLC, footswitch, cave, 2-hand-operation)
- 19" industrial housing (optional)
Test methods
- AC voltage: 0V - 5000V
- Resolution: 100V
- AC current: 0,1mA - 100mA
- Resolution: 2mA
- Accuracy: 2.5%
- Short current: 200mA
- Current range switchable:
- Range: 0 - 10mA
- Range: 0 - 100mA
- 50Hz and 60Hz
- Switchable tests:
- "test"
- "burn"
Technical data
- Optic and acoustic error message
- Zero voltage switch (protects your test object)
- 2 precise instruments 50 x 100 mm
- 3 signal lamps (operation, safety, HV)
- 2 buttons (operation, HV)
- Digital I/O:
- START / STOP
- PASS / FAIL
- Test in progress
- Terminals:
- 2 HV sockets potential free
- Warning lamp
- Foot switch, test-cage, light curtain, prod.-line, two-hand-operation
- Highest safety standard:
- Key switch preventing unauthorized use
- High voltage absolutely potential-free
- Two fold isolated transformer and measurement converter
- Status indication
- Socket for external pilot lamp
- Integrated warning buzzer
- Insulated sockets
- Security activation knob in compliance with VDE0104
- Supply: 230V, 50/60 Hz, 8A max.
- Operating temperature: +5° up to +45°
- Air humidity: 70% (non-condensing)
- Attitude: 2000m
- Compact industrial casing (W/H/D): 585/212/325 mm
- Weight: 21 kg
- CE-compliant, in accordance with EN 50 191
What's in the box:
- Safety circuit plug
- Power cable
- Operation manual
- Calibration certificate
Options
- HTP06N HV probe
- HVP06C HV cable with plug
- KLD-SW delphin clamp black
- WK28 warning lamp
- RC carrying handle (holder)
- HVS06N HV sockets backside
- UH28CS-R comfortable 19" rack housing
HV Test: | AC |
---|---|
Test current: | >3mA - 100mA |
Test voltage: | >3kV - 6kV |
Related products
- With safety socket and test nipple
- For easy testing of test objects
- In plastic casing
- Reliable HV Probe
- Highly flexible HV connecting cable
- Operating voltage 10 kVDC / 7 kVAC
- Hard-wearing tungsten test prod
- CE conformity, according EN 50 191
- Devices: 28 series
- Standard: EN 50191, VDE0104
- Lights: Red/Green
- Function: operation, switch on, ready
- Cable length: 2m
- All-Round-Test-Cage to connect
with safety testers and hipot testers - Dimension (W/H/D):
Outside: 450 / 515 / 495 mm
Inside: 360 / 350 / 450 mm - Viewable transparent swinging hood
- Damping gas spring
- Safety limit switch
- CE conform with EN 50191
- Hipot Tester: UH28C
- With foot protection cover
- Start via control-IO
- With plug: 12-pole
- Access to control interface
- Cable length: 2m
- Including cable set for hipot tester 28 series
- Start button
- Dimension (W/H/D):
Outside: 450 / 515 / 495 mm
Inside: 360 / 350 / 450 mm - Completely mounted and wired for plug&play
- PVC design-housing
- Viewable transparent swinging hood
- Damping gas spring
- Safety limit switch
- CE conform with EN 50191
- HV-Cable single-pole, yellow
- HV-Plug HVP06N
- 7 kV AC / 10 kV DC, max. 10 A
- HV-Cable single-pole, yellow
- HV-right angle plug HVP06NW
- 7 kV AC / 10 kV DC, max. 10 A
- Robust 2-wire matrix
- Measuring points freely connectable
- Test connection via Harting plug
- Continuity tests
- High voltage tests
- Insulation resistance tests
- Surge voltage tests
- Side mounting for test waggon or table
- Ergonomically placed
- HV probe type: HTP
- Side: right
- Colour: white
- Triangle design
- With flash arrow
- Material: plactic
- Size: 200mm x 200mm
- Colour: yellow/black
- DIN 40008
- Rectangle design
- "Danger High Voltage"
- Material: plactic
- Size: 74mm x 210mm
- Colour: yellow/black
- EN50191 / DIN 40008
- Portable posts chain
- Convex base plate
- Colour: Yellow-Black
- Two-parts
- Height: 1100mm / D=32cm
- Reliable HV Probe
- Highly flexible HV connecting cable
- Operating voltage 10 kVDC / 7 kVAC
- Hard-wearing tungsten test prod
- CE conformity, according EN 50 191
- With safety socket
- For easy testing of test objects
- L and N bridged/connected
- In plastic casing
- Standard-compliant, multi-vendor calibration based on ISO 17025
- Calibration of Hipot Tester / HV tester
- Traceable to DKD
- Cleaning and adjustment
- Repair service
- Including cable-set for hipot tester 28 series:
UH28C, UH28, UH28CS, A, M, P - Ergonomically design
- Push-start-buttons: 2
- Normed distance between buttons
- Connecting cable: 2.5 m
- Hipot Tester: UH28C
- Start via control-IO
- With plug: 12-pole
- Access to control interface
- Cable length: 2m
- HV-Cable single-pole, yellow
- HV-Plug HVP06N
- With contact terminal
- 7 kV AC / 10 kV DC, max. 10 A
- HV-Cable single-pole, yellow
- HV-Plug HVP06N
- opposite plug: lamellar plug
- 7 kV AC / 10 kV DC, max. 10 A
- Conforming to all standards
- Emergency stop for tester
- Load: 16 A
- Cable length: 5 m
- Side mounting for test waggon or table
- Ergonomically placed
- HV probe type: HTP
- Side: left
- Colour: white
- Rectangle design
- "No unauthorised entry"
- Material: plactic
- Size: 200mm x 300mm
- Colour: red/white
- Reliable HV Probe without plug
- Highly flexible HV connecting cable
- Operating voltage 10 kVDC / 7 kVAC
- Hard-wearing tungsten test prod
- CE conformity, according EN 50 191