If the error message E94 appears on the frequency converter display, it indicates that the threshold for the input voltage at analog input AI3 (panel potentiometer) has been undershot.
Causes:
The panel potentiometer is turned too far to the left or is defective.
P05.53=1, but no external control panel is connected.
Solutions:
Check whether the threshold voltage value in parameter P08.61 is set too high.
Check parameter P05.53.
If none of these issues apply, please contact technical support.