If the error message E92 appears on the frequency converter display, it indicates that the threshold for the input voltage at analog input AI1 has been undershot.
Causes:
The input voltage or current at AI1 is too low.
Nothing is connected to AI1.
Solutions:
Check the wiring of AI1.
Check whether the threshold voltage value in parameter P08.59 is set too high.
Check whether the position of the V/I switch matches the setting in P05.52.
Set parameter P05.52 to 0 and connect AI1 directly to the +10V source for testing.
If none of these issues apply, please contact technical support.